A/C PRESSURE TRANSDUCER

The A/C pressure transducer is tested using a scan tool. Refer to 9 - Engine Electrical Diagnostics for more information. Before testing the A/C pressure transducer, be certain that the transducer wire harness connection is clean of corrosion and properly connected. For the A/C to operate, an A/C pressure transducer voltage reading between 0.451 and 4.519 volts is required. Voltages outside this range indicate a low or high refrigerant system pressure condition to the powertrain control module (PCM). The PCM is programmed to respond to a low or high refrigerant system pressure by suppressing operation of the A/C compressor. Refer to the A/C Pressure Transducer Voltage chart for the possible conditions indicated by the transducer voltage reading.


A/C PRESSURE TRANSDUCER VOLTAGE

Voltage
 
Possible Indication
 
0.0
 
1. No sensor supply voltage from PCM.
 
  2. Shorted sensor circuit.
 
  3. Inoperative transducer.
 
0.150 TO 0.450
 
1. Ambient temperature below 10° C (50° F).
 
  2. Low refrigerant system pressure.
 
0.451 TO 4.519
 
1. Normal refrigerant system pressure.
 
4.520 TO 4.850
 
1. High refrigerant system pressure.
 
5.0
 
1. Open sensor circuit.
 
  2. Inoperative transducer.